Evaluation on the operation of Refrigerated Container Van IRCU200215-2 as per submitted data records
May 01, 2016 - Operation
is normal
May 02, 2016 - Operation
is normal until
Unit Power shutdown at 16:24H, no data recorded after shutdown
May 03, 2016 - Resume operation at 00:20H, unit was not in operation for
almost 8 hours from the time of shutdown on 5-02-16/16:24H.
From the recorded data shown 24hours, Supply air and Return air
was in
semi-abnormal mode, with this temperature, frozen meat were begin
to
melt.
01:00H to 20:00H -
(Semi-abnormal operation) Technician on duty who conducts every 3 hour
inspection should notice this activity and did some inspection inside the unit.
20:44H – Technician change the settings of DEFROST interval to 3 hours
21:21H – Initiated manual defrost
May 04, 2016 - The unit
was in semi abnormal state
Several manual defrost
was initiated
02:06 Initiated manual defrost
04:10 Initiated
manual defrost
08:45 Initiated manual defrost
10:34 Power Down
11:36 Power On
11:39 Manual Pre-Trip Initiated By Keypad - Test run
11:44 Initiated manual defrost
13:00H – 24:00H - Unit is
in Recovery Mode
May 05, 2016 - Unit is
in recovery mode (semi normal operation)
May 06, 2016 - Unit is
in recovery mode (semi normal operation)
May 07, 2016 - Unit is
in recovery mode (normal operation)
May 08, 2016 - Unit is
in recovery mode (normal operation)
May 09, 2016 - Unit is
in recovery mode (normal operation)
May 10, 2016 - Unit is
in recovery mode (normal operation)
May 11, 2016 - Unit is
in recovery mode (normal operation)
*Note: This is my only observation for reference use.
May 01, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
01:00 -24.72 -14.00
02:00 -25.23 -13.65
03:00 -26.01 -13.12
04:00 -26.80 -12.40
05:00 -27.43 -11.66
06:00 -24.62 -9.58
07:00 -15.21 -7.29
08:00 -22.62 -14.13
09:00 -22.43 -14.13
10:00 -23.59 -15.23
11:00 -23.88 -15.47 OPERATION IS NORMAL
12:00 -24.16 -15.63
13:00 -24.39 -15.71
14:00 -24.64 -15.71
15:00 -24.88 -15.69
16:00 -25.20 -15.73
17:00 -25.33 -15.55
18:00 -25.38 -15.33
19:00 -25.35 -15.35
20:00 -25.55 -14.79
21:00 -25.96 -14.37
22:00 -26.55 -13.62
23:00 -26.87 -12.63
24:00 -26.32 -11.55
May 01, 2016
Time Event Data
00:00 Controller Alarms: 53 - Battery Pack Failure
01:00 Controller Alarms: 53 - Battery Pack Failure
02:00 Controller Alarms: 53 - Battery Pack Failure
03:00 Controller Alarms: 53 - Battery Pack Failure
04:00 Controller Alarms: 53 - Battery Pack Failure
05:00 Controller Alarms: 53 - Battery Pack Failure
05:37 Defrost Initiated By Timer
05:37 Operating Mode Changed to Defrost
06:00 Controller Alarms: 53 - Battery Pack Failure
06:12 Defrost Terminated Due to Normal Operation
06:21 No Active DataCorder Alarms
06:21 Operating Mode Changed to Cool Reduced
06:23 Operating Mode Changed to Cool Max
07:00 Controller Alarms: 53 - Battery Pack Failure
08:00 Controller Alarms: 53 - Battery Pack Failure
08:01 Power Down (Battery Not Present)
08:09 Power On (Battery Not Present)
08:10 Operating Mode Changed to Cool Reduced
08:12 Operating Mode Changed to Cool Max
09:00 Controller Alarms: 53 - Battery Pack Failure
10:00 Controller Alarms: 53 - Battery Pack Failure
11:00 Controller Alarms: 53 - Battery Pack Failure
12:00 Controller Alarms: 53 - Battery Pack Failure
13:00 Controller Alarms: 53 - Battery Pack Failure
14:00 Controller Alarms: 53 - Battery Pack Failure
15:00 Controller Alarms: 53 - Battery Pack Failure
16:00 Controller Alarms: 53 - Battery Pack Failure
17:00 Controller Alarms: 53 - Battery Pack Failure
18:00 Controller Alarms: 53 - Battery Pack Failure
19:00 Controller Alarms: 53 - Battery Pack Failure
20:00 Controller Alarms: 53 - Battery Pack Failure
21:00 Controller Alarms: 53 - Battery Pack Failure
22:00 Controller Alarms: 53 - Battery Pack Failure
23:00 Controller Alarms: 53 - Battery Pack Failure
23:50 Defrost Initiated Due to Delta Temp
23:50 Operating Mode Changed to Defrost
_______________________________________________________
May 02, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
01:00 -12.46 -4.80
02:00 -21.77 -13.36
03:00 -22.97 -14.73
04:00 -23.53 -15.28
05:00 -23.81 -15.47
06:00 -24.05 -15.58
07:00 -24.35 -15.62 OPERATION IS NORMAL
08:00 -24.64 -15.66
09:00 -24.98 -15.70
10:00 -25.31 -15.72
11:00 -25.57 -15.65
12:00 -25.92 -15.61
13:00 -26.23 -15.99
14:00 -26.62 -15.71
15:00 -27.11 -15.40
16:00 -23.31 -10.38
May 02,2016
Time Event Data
00:00 Controller Alarms: 53 - Battery Pack Failure
00:00 Defrost Initiated - Active from Previous Day
00:29 Defrost Terminated Due to Normal Operation
00:37 Operating Mode Changed to Cool Reduced
00:39 Operating Mode Changed to Cool Max
01:00 Controller Alarms: 53 - Battery Pack Failure
02:00 Controller Alarms: 53 - Battery Pack Failure
03:00 Controller Alarms: 53 - Battery Pack Failure
04:00 Controller Alarms: 53 - Battery Pack Failure
05:00 Controller Alarms: 53 - Battery Pack Failure
06:00 Controller Alarms: 53 - Battery Pack Failure
07:00 Controller Alarms: 53 - Battery Pack Failure
08:00 Controller Alarms: 53 - Battery Pack Failure
09:00 Controller Alarms: 53 - Battery Pack Failure
10:00 Controller Alarms: 53 - Battery Pack Failure
11:00 Controller Alarms: 53 - Battery Pack Failure
12:00 Controller Alarms: 53 - Battery Pack Failure
13:00 Controller Alarms: 53 - Battery Pack Failure
14:00 Controller Alarms: 53 - Battery Pack Failure
15:00 Controller Alarms: 53 - Battery Pack Failure
15:30 Defrost Initiated Due to Delta Temp
15:30 Operating Mode Changed to Defrost
16:00 Controller Alarms: 53 - Battery Pack Failure
16:04 Defrost Terminated Due to Normal Operation
16:13 Operating Mode Changed to Cool Reduced
16:14 Operating Mode Changed to Cool Max
16:24 Power Down (Battery Not Present)
_______________________________________________________
May 03, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
01:00 -11.43 -3.91 Semi-abnormal operation
02:00 -16.05 -7.36
03:00 -17.29 -4.66
04:00 -7.65 1.35
05:00 -15.55 -6.48
06:00 -19.10 -7.67 Technician should begin
07:00 -10.27 -0.37 to check
the unit
08:00 -15.90 -6.72
09:00 -19.17 -7.99
10:00 -11.19 -1.37
11:00 -16.24 -6.66
12:00 -19.35 -8.26
13:00 -14.28 -2.33
14:00 -14.52 -6.17
15:00 -19.31 -8.11
16:00 -17.38 -5.40
17:00 -12.26 -3.73
18:00 -18.53 -7.61
19:00 -20.48 -7.50
Time Event Data
00:20 Power On (Battery Not Present)
00:20 Controller Alarms: 53 - Battery Pack Failure
00:22 Operating Mode Changed to Cool Reduced
00:45 Operating Mode Changed to Cool Max
01:00 Controller Alarms: 53 - Battery Pack Failure
02:00 Controller Alarms: 53 - Battery Pack Failure
03:00 Controller Alarms: 53 - Battery Pack Failure
03:10 Defrost Initiated Due to Delta Temp
03:46 Defrost Terminated Due to Normal Operation
03:55 Operating Mode Changed to Modulated Cool
03:55 Operating Mode Changed to Cool Reduced
04:00 Controller Alarms: 53 - Battery Pack Failure
04:15 Operating Mode Changed to Cool Max
05:00 Controller Alarms: 53 - Battery Pack Failure
06:00 Controller Alarms: 53 - Battery Pack Failure
06:12 Defrost Initiated Due to Delta Temp
06:48 Defrost Terminated Due to Normal Operation
06:56 Operating Mode Changed to High Speed Evaps
06:56 Operating Mode Changed to Cool Reduced
07:00 Controller Alarms: 53 - Battery Pack Failure
07:17 Operating Mode Changed to Cool Max
08:00 Controller Alarms: 53 - Battery Pack Failure
09:00 Controller Alarms: 53 - Battery Pack Failure
09:14 Defrost Initiated Due to Delta Temp
09:49 Defrost Terminated Due to Normal Operation
09:57 Operating Mode Changed to High Speed Evaps
09:58 Operating Mode Changed to Cool Reduced
10:00 Controller Alarms: 53 - Battery Pack Failure
10:17 Operating Mode Changed to Cool Max
11:00 Controller Alarms: 53 - Battery Pack Failure
12:00 Controller Alarms: 53 - Battery Pack Failure
12:22 Defrost Initiated Due to Delta Temp
12:22 Operating Mode Changed to Defrost
12:57 Defrost Terminated Due to Normal Operation
13:00 Controller Alarms: 53 - Battery Pack Failure
13:06 Operating Mode Changed to Cool Reduced
13:07 Operating Mode Changed to Cool Max
14:00 Controller Alarms: 53 - Battery Pack Failure
15:00 Controller Alarms: 53 - Battery Pack Failure
15:32 Defrost Initiated Due to Delta Temp
15:32 Operating Mode Changed to Defrost
16:00 Controller Alarms: 53 - Battery Pack Failure
16:06 Defrost Terminated Due to Normal Operation
16:15 Operating Mode Changed to Cool Reduced
16:16 Operating Mode Changed to Cool Max
17:00 Controller Alarms: 53 - Battery Pack Failure
18:00 Controller Alarms: 53 - Battery Pack Failure
18:57 Defrost Initiated Due to Delta Temp
18:57 Operating Mode Changed to Defrost
19:00 Controller Alarms: 53 - Battery Pack Failure
19:32 Defrost Terminated Due to Normal Operation
_______________________________________________________
May 03, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
20:00 -9.43 -0.63
22:00 -3.14 2.52
23:00 -15.70 -5.84
24:00 -18.05 -7.25
May 03, 2016
Time Event Data
19:40 Operating Mode Changed to Cool Reduced
19:58 Operating Mode Changed to Cool Max
20:00 Controller Alarms: 53 - Battery Pack Failure
20:44 User Selectable
Change: Defrost Interval changed to 3 hours By Keypad
20:45 Power Down (Battery Not Present)
21:19 Power On (Battery Not Present)
21:20 Controller Alarms: 53 - Battery Pack Failure
21:21 Defrost Initiated By Keypad - Manual Defrost
21:48 Defrost Terminated Due to Normal Operation
21:56 Operating Mode Changed to Modulated Cool
21:56 Operating Mode Changed to Cool Reduced
22:00 Controller Alarms: 53 - Battery Pack Failure
22:19 Operating Mode Changed to Cool Max
23:00 Controller Alarms: 53 - Battery Pack Failure
_______________________________________________________
May 04, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
01:00 -19.65 -6.83
02:00 -9.00 -0.16 - Manual Defrost
03:00 -9.01 -0.49 Semi-abnormal
operation
04:00 -17.01 -6.75
05:00 -10.21 -1.76 - Manual Defrost
06:00 -17.43 -6.94
07:00 -19.30 -8.36
08:00 -20.53 -8.61
09:00 -8.73 -1.00
10:00 -11.52 -2.34
12:00 -3.96 -2.73
May 04,2016
Time Event Data
00:00 Controller Alarms: 53 - Battery Pack Failure
00:51 Defrost Initiated Due to Delta Temp
00:51 Operating Mode Changed to Defrost
01:00 Controller Alarms: 53 - Battery Pack Failure
01:28 Defrost Terminated Due to Normal Operation
01:37 Operating Mode Changed to Modulated Cool
01:37 Operating Mode Changed to Cool Reduced
02:00 Controller Alarms: 53 - Battery Pack Failure
02:06 Defrost Initiated By Keypad
-
Manual Defrost
02:35 Defrost Terminated Due to Normal Operation
02:44 Operating Mode Changed to Modulated Cool
02:44 Operating Mode Changed to Cool Reduced
03:00 Controller Alarms: 53 - Battery Pack Failure
03:06 Operating Mode Changed to Cool Max
04:00 Controller Alarms: 53 - Battery Pack Failure
04:10 Defrost Initiated By Keypad - Manual Defrost
04:42 Defrost Terminated Due to Normal Operation
04:50 Operating Mode Changed to Modulated Cool
04:50 Operating Mode Changed to Cool Reduced
05:00 Controller Alarms: 53 - Battery Pack Failure
05:12 Operating Mode Changed to Cool Max
06:00 Controller Alarms: 53 - Battery Pack Failure
07:00 Controller Alarms: 53 - Battery Pack Failure
07:51 Defrost Initiated By Timer
07:51 Operating Mode Changed to Defrost
08:00 Controller Alarms: 53 - Battery Pack Failure
08:28 Defrost Terminated Due to Normal Operation
08:39 Operating Mode Changed to Cool Max
08:45 Defrost Initiated By Keypad - Manual Defrost
08:45 Operating Mode Changed to Defrost
09:00 Controller Alarms: 53 - Battery Pack Failure
09:12 Defrost Terminated Due to Normal Operation
09:21 Operating Mode Changed to Cool Reduced
09:29 Operating Mode Changed to Cool Max
10:00 Controller Alarms: 53 - Battery Pack Failure
10:34 Power Down (Battery Not Present)
11:36 Power On (Battery Not Present)
11:36 Controller Alarms: 53 - Battery Pack Failure
11:37 Power Down (Battery Not Present)
11:37 Power On (Battery Not Present)
11:39 Manual Pre-Trip Initiated
By Keypad
11:41 P3-0 Low Evap On Test: Passed- A: 1.50, B: 2.05, C: 1.50
P3-1 Low Evap Off
Test: Passed- A: 1.50, B: 2.03, C: 1.50
11:42 P4-0 High Evap On Test: Passed- A: 1.56, B: 2.77, C: 1.56,
Ratio: 1.77
P4-1 High Evap Off
Test: Passed- A: 1.55, B: 2.77, C: 1.55
P4-2 Remote Evap Fans
On Test: Not Run
11:42 Pre-Trip Test Termination
P1-0: Not Run P1-1:
Not Run P1-2: Not Run
P2-0: Not Run P2-1:
Not Run
P3-0: Passed P3-1:
Passed
P4-0: Passed P4-1:
Passed P4-2: Not Run
P5-0: Not Run P5-1:
Not Run P5-2: Not Run P5-3: Not Run P5-4: Not Run
P5-5: Not Run
P5-6: Not Run P5-7: Not Run P5-8: Not Run
P5-9: Not Run P5-10: Not Run P5-11: Not
Run P5-12: Not Run
P6-0: Not Run P6-1:
Not Run P6-2: Not Run P6-3: Not Run P6-4: Not Run
P6-5: Not Run
P6-6: Not Run P6-7: Not Run P6-8: Not Run
P6-9: Not Run
P6-10: Not Run P6-11: Not Run
P7-0: Not Run P7-1:
Not Run
P8-0: Not Run P8-1:
Not Run P8-2: Not Run
P9-0: Not Run
P10-0: Not Run P10-1:
Not Run P10-2: Not Run
11:43 Operating Mode Changed to Cool Reduced
11:44 Defrost Initiated By Keypad
11:44 Operating Mode Changed to Defrost
12:00 Controller Alarms: 53 - Battery Pack Failure
12:13 Defrost Terminated Due to Normal Operation
12:21 Operating Mode Changed to High Speed Evaps
_______________________________________________________
May 04, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
13:00 -10.93 -2.26
14:00 -19.17 -8.53
15:00 -21.17 -9.66
16:00 -16.51 -3.38
17:00 -14.77 -6.78
18:00 -18.81 -8.20
19:00 -10.55
-2.38
20:00 -17.79 -7.63
21:00 -19.17 -8.31
22:00 -17.80 -7.20
23:00 -11.88 -3.82
24:00 -17.86 -7.51
May 04, 2016
Time Event Data
12:21 Operating Mode Changed to Cool Reduced
12:23 Operating Mode Changed to Cool Max
13:00 Controller Alarms: 53 - Battery Pack Failure
14:00 Controller Alarms: 53 - Battery Pack Failure
15:00 Controller Alarms: 53 - Battery Pack Failure
15:22 Defrost Initiated By Timer
15:22 Operating Mode Changed to Defrost
15:59 Defrost Terminated Due to Normal Operation
16:00 Controller Alarms: 53 - Battery Pack Failure
16:07 Operating Mode Changed to Cool Reduced
16:27 Operating Mode Changed to Cool Max
17:00 Controller Alarms: 53 - Battery Pack Failure
17:56 Defrost Initiated By Keypad
17:56 Operating Mode Changed to Defrost
18:00 Controller Alarms: 53 - Battery Pack Failure
18:27 Defrost Terminated Due to Normal Operation
18:36 Operating Mode Changed to Cool Reduced
18:56 Operating Mode Changed to Cool Max
19:00 Controller Alarms: 53 - Battery Pack Failure
20:00 Controller Alarms: 53 - Battery Pack Failure
21:00 Controller Alarms: 53 - Battery Pack Failure
21:37 Defrost Initiated By Timer
21:37 Operating Mode Changed to Defrost
22:00 Controller Alarms: 53 - Battery Pack Failure
22:11 Defrost Terminated Due to Normal Operation
22:20 Operating Mode Changed to Cool Reduced
22:38 Operating Mode Changed to Cool Max
23:00 Controller Alarms: 53 - Battery Pack Failure
23:53 Defrost Initiated By Keypad
23:53 Operating Mode Changed to Defrost
_______________________________________________________
May 05, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
01:00 -10.54 -1.91
02:00 -18.60 -8.12
03:00 -20.30 -9.18
04:00 -18.75
-7.29
05:00 -13.17 -4.74
06:00 -19.32 -8.81
07:00 -20.47 -9.68
08:00 -11.53 -2.55
09:00 -18.97 -8.83
10:00 -20.10 -9.54
11:00 -19.88 -9.46
12:00 -12.08 -3.20
13:00 -19.53 -9.24
14:00 -20.54 -9.86
15:00 -18.19 -7.98
16:00 -13.75 -3.71
17:00 -19.60 -9.40
18:00 -10.81 0.57
19:00 -18.27 -8.69
20:00 -19.63 -9.30
May 05, 2016
Time Event Data
00:00 Controller Alarms: 53 - Battery Pack Failure
00:00 Defrost Initiated - Active from Previous Day
00:24 Defrost Terminated Due to Normal Operation
00:33 Operating Mode Changed to Cool Reduced
00:53 Operating Mode Changed to Cool Max
01:00 Controller Alarms: 53 - Battery Pack Failure
02:00 Controller Alarms: 53 - Battery Pack Failure
03:00 Controller Alarms: 53 - Battery Pack Failure
03:35 Defrost Initiated By Timer
03:35 Operating Mode Changed to Defrost
04:00 Controller Alarms: 53 - Battery Pack Failure
04:10 Defrost Terminated Due to Normal Operation
04:18 Operating Mode Changed to Cool Reduced
04:36 Operating Mode Changed to Cool Max
05:00 Controller Alarms: 53 - Battery Pack Failure
06:00 Controller Alarms: 53 - Battery Pack Failure
07:00 Controller Alarms: 53 - Battery Pack Failure
07:00 Defrost Initiated By Keypad
07:35 Defrost Terminated Due to Normal Operation
07:43 Operating Mode Changed to High Speed Evaps
07:43 Operating Mode Changed to Cool Reduced
08:00 Controller Alarms: 53 - Battery Pack Failure
08:03 Operating Mode Changed to Cool Max
09:00 Controller Alarms: 53 - Battery Pack Failure
10:00 Controller Alarms: 53 - Battery Pack Failure
10:45 Defrost Initiated By Timer
10:45 Operating Mode Changed to Defrost
11:00 Controller Alarms: 53 - Battery Pack Failure
11:21 Defrost Terminated Due to Normal Operation
11:30 Operating Mode Changed to Cool Reduced
11:31 Operating Mode Changed to Cool Max
12:00 Controller Alarms: 53 - Battery Pack Failure
13:00 Controller Alarms: 53 - Battery Pack Failure
14:00 Controller Alarms: 53 - Battery Pack Failure
14:32 Defrost Initiated By Timer
14:32 Operating Mode Changed to Defrost
15:00 Controller Alarms: 53 - Battery Pack Failure
15:10 Defrost Terminated Due to Normal Operation
15:19 Operating Mode Changed to Cool Reduced
15:21 Operating Mode Changed to Cool Max
16:00 Controller Alarms: 53 - Battery Pack Failure
17:00 Controller Alarms: 53 - Battery Pack Failure
17:05 Defrost Initiated By Keypad
17:43 Defrost Terminated Due to Normal Operation
17:52 Operating Mode Changed to Modulated Cool
17:52 Operating Mode Changed to Cool Reduced
18:00 Controller Alarms: 53 - Battery Pack Failure
18:15 Operating Mode Changed to Cool Max
19:00 Controller Alarms: 53 - Battery Pack Failure
20:00 Controller Alarms: 53 - Battery Pack Failure
_______________________________________________________
May 05, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
21:00 -20.28 -10.09
22:00 -11.07 -2.03
23:00 -18.53 -8.92
24:00 -19.27 -9.31
May 05, 2016
Time Event Data
20:54 Defrost Initiated By Timer
20:54 Operating Mode Changed to Defrost
21:00 Controller Alarms: 53 - Battery Pack Failure
21:29 Defrost Terminated Due to Normal Operation
21:38 Operating Mode Changed to Modulated Cool
21:38 Operating Mode Changed to Cool Reduced
22:00 Controller Alarms: 53 - Battery Pack Failure
22:03 Operating Mode Changed to Cool Max
23:00 Controller Alarms: 53 - Battery Pack Failure
_______________________________________________________
May 06, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
01:00 -18.31 -8.52
02:00 -12.22 -3.17
03:00 -18.87 -8.91
08:00 -7.53 0.24
09:00 -15.25 -7.60
10:00 -19.30 -9.82
11:00 -20.68 -10.53
12:00 -13.45 -5.88
13:00 -19.27 -9.70
14:00 -20.20 -10.71
15:00 -19.82 -10.73
16:00 -14.58 -6.83
17:00 -19.89 -10.67
18:00 -20.10 -11.20
19:00 -14.13 -6.70
20:00 -18.35 -9.44
21:00 -19.74 -10.48
22:00 -20.41 -11.52
May 06, 2016
Time Event Data
00:00 Controller Alarms: 53 - Battery Pack Failure
00:40 Defrost Initiated By Timer
00:40 Operating Mode Changed to Defrost
01:00 Controller Alarms: 53 - Battery Pack Failure
01:16 Defrost Terminated Due to Normal Operation
01:25 Operating Mode Changed to Cool Reduced
01:44 Operating Mode Changed to Cool Max
02:00 Controller Alarms: 53 - Battery Pack Failure
03:00 Controller Alarms: 53 - Battery Pack Failure
03:29 Power Down (Battery Not Present)
07:26 Power On (Battery Not Present)
07:27 Controller Alarms: 53 - Battery Pack Failure
07:27 Operating Mode Changed to Cool Reduced
07:33 Defrost Initiated By Keypad
07:33 Operating Mode Changed to Defrost
07:57 Defrost Terminated Due to Normal Operation
08:00 Controller Alarms: 53 - Battery Pack Failure
08:06 Operating Mode Changed to Cool Reduced
08:26 Operating Mode Changed to Cool Max
09:00 Controller Alarms: 53 - Battery Pack Failure
10:00 Controller Alarms: 53 - Battery Pack Failure
11:00 Controller Alarms: 53 - Battery Pack Failure
11:07 Defrost Initiated By Timer
11:34 Defrost Terminated Due to Normal Operation
11:42 Operating Mode Changed to High Speed Evaps
11:43 Operating Mode Changed to Cool Reduced
12:00 Controller Alarms: 53 - Battery Pack Failure
12:02 Operating Mode Changed to Cool Max
13:00 Controller Alarms: 53 - Battery Pack Failure
14:00 Controller Alarms: 53 - Battery Pack Failure
14:44 Defrost Initiated By Timer
14:44 Operating Mode Changed to Defrost
15:00 Controller Alarms: 53 - Battery Pack Failure
15:11 Defrost Terminated Due to Normal Operation
15:20 Operating Mode Changed to Cool Reduced
15:25 Operating Mode Changed to Cool Max
16:00 Controller Alarms: 53 - Battery Pack Failure
17:00 Controller Alarms: 53 - Battery Pack Failure
18:00 Controller Alarms: 53 - Battery Pack Failure
18:21 Defrost Initiated By Timer
18:47 Defrost Terminated Due to Normal Operation
18:56 Operating Mode Changed to Modulated Cool
18:56 Operating Mode Changed to Cool Reduced
19:00 Controller Alarms: 53 - Battery Pack Failure
19:19 Operating Mode Changed to Cool Max
20:00 Controller Alarms: 53 - Battery Pack Failure
21:00 Controller Alarms: 53 - Battery Pack Failure
21:58 Defrost Initiated By Timer
21:58 Operating Mode Changed to Defrost
22:00 Controller Alarms: 53 - Battery Pack Failure
22:25 Defrost Terminated Due to Normal Operation
22:33 Operating Mode Changed to High Speed Evaps
_______________________________________________________
May 06, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
23:00 -12.95 -5.66
24:00 -18.74 -10.03
May 06, 2016
Time Event Data
22:33 Operating Mode Changed to Modulated Cool
22:34 Operating Mode Changed to Cool Reduced
23:00 Controller Alarms: 53 - Battery Pack Failure
23:00 Operating Mode Changed to Cool Max
_______________________________________________________
May 07, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
01:00 -19.29 -10.51
02:00 -17.41 -8.29
03:00 -15.16 -8.51
04:00 -13.76 -5.43
05:00 -18.92 -10.20
06:00 -20.35 -11.16
07:00 -21.13 -12.13
08:00 -14.10 -6.49
09:00 -20.42 -11.37
10:00 -21.04 -11.92
11:00 -19.05 -9.98
12:00 -16.46 -8.97
13:00 -21.05 -12.10
15:00 -18.03 -9.30
16:00 -21.77 -12.35
17:00 -19.35 -9.37
18:00 -16.20 -8.67
19:00 -20.63 -11.39
20:00 -20.82 -11.71
May 07, 2016
Time Event Data
00:00 Controller Alarms: 53 - Battery Pack Failure
01:00 Controller Alarms: 53 - Battery Pack Failure
01:35 Defrost Initiated By Timer
01:35 Operating Mode Changed to Defrost
02:00 Controller Alarms: 53 - Battery Pack Failure
02:01 Defrost Terminated Due to Normal Operation
02:09 Operating Mode Changed to Cool Reduced
02:31 Operating Mode Changed to Cool Max
03:00 Controller Alarms: 53 - Battery Pack Failure
03:22 Defrost Initiated By Keypad
03:47 Defrost Terminated Due to Normal Operation
03:55 Operating Mode Changed to Modulated Cool
03:55 Operating Mode Changed to Cool Reduced
04:00 Controller Alarms: 53 - Battery Pack Failure
04:15 Operating Mode Changed to Cool Max
05:00 Controller Alarms: 53 - Battery Pack Failure
06:00 Controller Alarms: 53 - Battery Pack Failure
06:58 Defrost Initiated By Timer
06:58 Operating Mode Changed to Defrost
07:00 Controller Alarms: 53 - Battery Pack Failure
07:25 Defrost Terminated Due to Normal Operation
07:33 Operating Mode Changed to Cool Reduced
07:52 Operating Mode Changed to Cool Max
08:00 Controller Alarms: 53 - Battery Pack Failure
09:00 Controller Alarms: 53 - Battery Pack Failure
10:00 Controller Alarms: 53 - Battery Pack Failure
10:36 Defrost Initiated By Timer
10:36 Operating Mode Changed to Defrost
11:00 Controller Alarms: 53 - Battery Pack Failure
11:03 Defrost Terminated Due to Normal Operation
11:11 Operating Mode Changed to Cool Reduced
11:30 Operating Mode Changed to Cool Max
12:00 Controller Alarms: 53 - Battery Pack Failure
13:00 Controller Alarms: 53 - Battery Pack Failure
13:06 Power Down (Battery Not Present)
14:33 Power On (Battery Not Present)
14:33 Controller Alarms: 53 - Battery Pack Failure
14:34 Operating Mode Changed to Cool Reduced
14:35 Operating Mode Changed to Cool Max
15:00 Controller Alarms: 53 - Battery Pack Failure
16:00 Controller Alarms: 53 - Battery Pack Failure
16:33 Defrost Initiated By Keypad
16:33 Operating Mode Changed to Defrost
17:00 Controller Alarms: 53 - Battery Pack Failure
17:02 Defrost Terminated Due to Normal Operation
17:11 Operating Mode Changed to Cool Reduced
17:12 Operating Mode Changed to Cool Max
18:00 Controller Alarms: 53 - Battery Pack Failure
19:00 Controller Alarms: 53 - Battery Pack Failure
20:00 Controller Alarms: 53 - Battery Pack Failure
20:13 Defrost Initiated By Timer
20:13 Operating Mode Changed to Defrost
20:42 Defrost Terminated Due to Normal Operation
_______________________________________________________
May 07, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
21:00 -13.84 -4.75
22:00 -19.30 -10.57
23:00 -18.97 -10.29
24:00 -14.03 -4.67
May 07, 2016
Time Event Data
20:51 Operating Mode Changed to Cool Reduced
20:55 Operating Mode Changed to Cool Max
21:00 Controller Alarms: 53 - Battery Pack Failure
22:00 Controller Alarms: 53 - Battery Pack Failure
22:46 Defrost Initiated By Keypad
22:46 Operating Mode Changed to Defrost
23:00 Controller Alarms: 53 - Battery Pack Failure
23:13 Defrost Terminated Due to Normal Operation
23:21 Operating Mode Changed to Cool Reduced
23:23 Operating Mode Changed to Cool Max
_______________________________________________________
May 08, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
01:00 -19.57 -10.76
02:00 -20.17 -11.32
03:00 -14.65 -5.42
04:00 -18.92 -10.45
05:00 -20.92 -11.67
06:00 -21.62 -12.20
07:00 -14.34 -5.31
08:00 -14.17 -5.11
09:00 -20.99 -11.74
10:00 -19.70 -10.21
11:00 -16.31 -7.00
12:00 -21.63 -12.24
13:00 -22.23 -12.81
14:00 -15.56
-6.30
15:00 -21.11 -12.01
16:00 -22.29 -12.94
17:00 -21.33 -12.42
18:00 -15.46 -5.86
19:00 -18.90 -8.59
May 08, 2016
Time Event Data
00:00 Controller Alarms: 53 - Battery Pack Failure
01:00 Controller Alarms: 53 - Battery Pack Failure
02:00 Controller Alarms: 53 - Battery Pack Failure
02:23 Defrost Initiated By Timer
02:23 Operating Mode Changed to Defrost
02:51 Defrost Terminated Due to Normal Operation
02:59 Operating Mode Changed to High Speed Evaps
03:00 Controller Alarms: 53 - Battery Pack Failure
03:00 Operating Mode Changed to Cool Reduced
03:02 Operating Mode Changed to Cool Max
04:00 Controller Alarms: 53 - Battery Pack Failure
05:00 Controller Alarms: 53 - Battery Pack Failure
06:00 Controller Alarms: 53 - Battery Pack Failure
06:02 Defrost Initiated By Timer
06:31 Defrost Terminated Due to Normal Operation
06:40 Operating Mode Changed to Cool Reduced
06:41 Operating Mode Changed to Cool Max
07:00 Controller Alarms: 53 - Battery Pack Failure
07:02 Defrost Initiated By Keypad
07:26 Defrost Terminated Due to Normal Operation
07:35 Operating Mode Changed to Cool Reduced
07:36 Operating Mode Changed to Cool Max
08:00 Controller Alarms: 53 - Battery Pack Failure
09:00 Controller Alarms: 53 - Battery Pack Failure
09:38 Defrost Initiated By Keypad
09:38 Operating Mode Changed to Defrost
10:00 Controller Alarms: 53 - Battery Pack Failure
10:07 Defrost Terminated Due to Normal Operation
10:15 Operating Mode Changed to Cool Reduced
10:17 Operating Mode Changed to Cool Max
11:00 Controller Alarms: 53 - Battery Pack Failure
12:00 Controller Alarms: 53 - Battery Pack Failure
13:00 Controller Alarms: 53 - Battery Pack Failure
13:17 Defrost Initiated By Timer
13:47 Defrost Terminated Due to Normal Operation
13:56 Operating Mode Changed to Cool Reduced
13:57 Operating Mode Changed to Cool Max
14:00 Controller Alarms: 53 - Battery Pack Failure
15:00 Controller Alarms: 53 - Battery Pack Failure
16:00 Controller Alarms: 53 - Battery Pack Failure
16:45 Defrost Initiated By Keypad
16:45 Operating Mode Changed to Defrost
17:00 Controller Alarms: 53 - Battery Pack Failure
17:13 Defrost Terminated Due to Normal Operation
17:22 Operating Mode Changed to Cool Reduced
17:24 Operating Mode Changed to Cool Max
18:00 Controller Alarms: 53 - Battery Pack Failure
18:38 Defrost Initiated By Keypad
18:38 Operating Mode Changed to Defrost
19:00 Controller Alarms: 53 - Battery Pack Failure
19:03 Defrost Terminated Due to Normal Operation
_______________________________________________________
May 08, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
20:00 -15.96 -7.93
21:00 -20.61 -11.57
22:00 -20.97 -12.35
23:00 -14.24 -5.23
24:00 -19.47 -10.89
May 08, 2016
Time Event Data
19:12 Operating Mode Changed to Cool Reduced
19:14 Operating Mode Changed to Cool Max
20:00 Controller Alarms: 53 - Battery Pack Failure
21:00 Controller Alarms: 53 - Battery Pack Failure
22:00 Controller Alarms: 53 - Battery Pack Failure
22:14 Defrost Initiated By Timer
22:43 Defrost Terminated Due to Normal Operation
22:52 Operating Mode Changed to Cool Reduced
22:56 Operating Mode Changed to Cool Max
23:00 Controller Alarms: 53 - Battery Pack Failure
_______________________________________________________
May 09, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
01:00 -20.26 -11.49
02:00 -20.58 -12.14
03:00 -13.78 -4.75
07:00 -19.09 -10.13
08:00 -21.74 -12.27
09:00 -22.53 -13.63
10:00 -15.22 -6.40
11:00 -21.43 -12.08
12:00 -22.24 -12.84
13:00 -21.97 -12.95
14:00 -15.62 -6.00
15:00 -17.73 -10.43
16:00 -22.35 -12.93
17:00 -21.80 -12.87
18:00 -14.97 -5.34
19:00 -15.31 -5.80
20:00 -21.07 -11.97
21:00 -21.23 -12.55
May 09, 2016
Time Event Data
00:00 Controller Alarms: 53 - Battery Pack Failure
01:00 Controller Alarms: 53 - Battery Pack Failure
01:53 Defrost Initiated By Timer
01:53 Operating Mode Changed to Defrost
02:00 Controller Alarms: 53 - Battery Pack Failure
02:21 Defrost Terminated Due to Normal Operation
02:30 Operating Mode Changed to Cool Reduced
02:49 Operating Mode Changed to Cool Max
03:00 Controller Alarms: 53 - Battery Pack Failure
03:45 Power Down (Battery Not Present)
06:04 Power On (Battery Not Present)
06:05 Controller Alarms: 53 - Battery Pack Failure
06:05 Operating Mode Changed to Cool Reduced
06:07 Operating Mode Changed to Cool Max
07:00 Controller Alarms: 53 - Battery Pack Failure
08:00 Controller Alarms: 53 - Battery Pack Failure
09:00 Controller Alarms: 53 - Battery Pack Failure
09:07 Defrost Initiated By Timer
09:38 Defrost Terminated Due to Normal Operation
09:46 Operating Mode Changed to Cool Reduced
09:48 Operating Mode Changed to Cool Max
10:00 Controller Alarms: 53 - Battery Pack Failure
11:00 Controller Alarms: 53 - Battery Pack Failure
12:00 Controller Alarms: 53 - Battery Pack Failure
12:48 Defrost Initiated By Timer
12:49 Operating Mode Changed to Defrost
13:00 Controller Alarms: 53 - Battery Pack Failure
13:18 Defrost Terminated Due to Normal Operation
13:27 Operating Mode Changed to Cool Reduced
13:29 Operating Mode Changed to Cool Max
14:00 Controller Alarms: 53 - Battery Pack Failure
14:24 Power Down (Battery Not Present)
14:50 Power On (Battery Not Present)
14:51 Operating Mode Changed to Cool Reduced
14:52 Operating Mode Changed to Cool Max
15:00 Controller Alarms: 53 - Battery Pack Failure
16:00 Controller Alarms: 53 - Battery Pack Failure
16:46 Defrost Initiated By Keypad
16:46 Operating Mode Changed to Defrost
17:00 Controller Alarms: 53 - Battery Pack Failure
17:16 Defrost Terminated Due to Normal Operation
17:26 Operating Mode Changed to Cool Max
17:47 Defrost Initiated By Keypad
17:47 Operating Mode Changed to Defrost
18:00 Controller Alarms: 53 - Battery Pack Failure
18:12 Defrost Terminated Due to Normal Operation
18:21 Operating Mode Changed to Cool Reduced
18:41 Operating Mode Changed to Cool Max
19:00 Controller Alarms: 53 - Battery Pack Failure
20:00 Controller Alarms: 53 - Battery Pack Failure
21:00 Controller Alarms: 53 - Battery Pack Failure
21:23 Defrost Initiated By Timer
21:23 Operating Mode Changed to Defrost
21:51 Defrost Terminated Due to Normal Operation
_______________________________________________________
May 09, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
22:00 -15.49 -6.33
23:00 -18.95 -10.89
24:00 -20.44 -11.81
May 09, 2016
Time Event Data
21:59 Operating Mode Changed to High Speed Evaps
22:00 Controller Alarms: 53 - Battery Pack Failure
22:00 Operating Mode Changed to Cool Reduced
22:14 Operating Mode Changed to Cool Max
23:00 Controller Alarms: 53 - Battery Pack Failure
_______________________________________________________
May 10, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
01:00 -20.78 -12.24
02:00 -13.80 -4.70
03:00 -20.49 -11.77
04:00 -21.47 -12.50
05:00 -20.39 -11.79
06:00 -15.93 -6.62
07:00 -21.75 -13.01
08:00 -22.31 -13.48
09:00 -16.37 -6.46
10:00 -20.81 -12.42
11:00 -15.59 -5.90
12:00 -21.81 -12.75
13:00 -22.59 -13.53
May 10, 2016
Time Event Data
00:00 Controller Alarms: 53 - Battery Pack Failure
01:00 Controller Alarms: 53 - Battery Pack Failure
01:02 Defrost Initiated By Timer
01:30 Defrost Terminated Due to Normal Operation
01:39 Operating Mode Changed to Cool Reduced
01:41 Operating Mode Changed to Cool Max
02:00 Controller Alarms: 53 - Battery Pack Failure
03:00 Controller Alarms: 53 - Battery Pack Failure
04:00 Controller Alarms: 53 - Battery Pack Failure
04:41 Defrost Initiated By Timer
04:41 Operating Mode Changed to Defrost
05:00 Controller Alarms: 53 - Battery Pack Failure
05:10 Defrost Terminated Due to Normal Operation
05:19 Operating Mode Changed to Cool Reduced
05:20 Operating Mode Changed to Cool Max
06:00 Controller Alarms: 53 - Battery Pack Failure
07:00 Controller Alarms: 53 - Battery Pack Failure
08:00 Controller Alarms: 53 - Battery Pack Failure
08:21 Defrost Initiated By Timer
08:21 Operating Mode Changed to Defrost
08:51 Defrost Terminated Due to Normal Operation
08:59 Operating Mode Changed to High Speed Evaps
09:00 Controller Alarms: 53 - Battery Pack Failure
09:00 Operating Mode Changed to Cool Reduced
09:02 Operating Mode Changed to Cool Max
10:00 Controller Alarms: 53 - Battery Pack Failure
10:09 Defrost Initiated By Keypad
10:36 Defrost Terminated Due to Normal Operation
10:45 Operating Mode Changed to Cool Reduced
10:47 Operating Mode Changed to Cool Max
11:00 Controller Alarms: 53 - Battery Pack Failure
12:00 Controller Alarms: 53 - Battery Pack Failure
13:00 Controller Alarms: 53 - Battery Pack Failure
13:33 Power Down (Battery Not Present)
_______________________________________________________
May 11, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: IRCU200215-2,
Serial : 04102615
Time SupAir RetAir
01:00 -11.80 -5.71
02:00 -16.86 -9.69
04:00 -13.20 -7.12
05:00 -17.97 -10.23
06:00 -19.87 -7.51
07:00 -14.65 -2.10
08:00 -12.54 -4.22
09:00 -19.20 -10.60
10:00 -21.46 -9.43
11:00 -15.09 -2.36
12:00 -16.17 -9.77
13:00 -19.73 -11.40
14:00 -21.58 -10.92
15:00 -12.92 -3.52
16:00 -19.06 -10.37
17:00 -20.35 -11.89
18:00 -20.94 -10.97
19:00 -9.07 0.43
May 11, 2016
Time Event Data
00:19 Power On (Battery Not Present)
00:20 Controller Alarms: 53 - Battery Pack Failure
00:20 Operating Mode Changed to Cool Reduced
00:33 Operating Mode Changed to Cool Max
01:00 Controller Alarms: 53 - Battery Pack Failure
02:00 Controller Alarms: 53 - Battery Pack Failure
02:39 Power Down (Battery Not Present)
03:23 Power On (Battery Not Present)
03:23 Controller Alarms: 53 - Battery Pack Failure
03:24 Operating Mode Changed to Cool Reduced
03:29 Operating Mode Changed to Cool Max
04:00 Controller Alarms: 53 - Battery Pack Failure
05:00 Controller Alarms: 53 - Battery Pack Failure
06:00 Controller Alarms: 53 - Battery Pack Failure
06:26 Defrost Initiated By Timer
06:26 Operating Mode Changed to Defrost
07:00 Controller Alarms: 53 - Battery Pack Failure
07:08 Defrost Terminated Due to Normal Operation
07:17 Operating Mode Changed to Cool Reduced
07:19 Operating Mode Changed to Cool Max
08:00 Controller Alarms: 53 - Battery Pack Failure
09:00 Controller Alarms: 53 - Battery Pack Failure
10:00 Controller Alarms: 53 - Battery Pack Failure
10:19 Defrost Initiated By Timer
10:19 Operating Mode Changed to Defrost
10:56 Defrost Terminated Due to Normal Operation
11:00 Controller Alarms: 53 - Battery Pack Failure
11:05 Operating Mode Changed to Cool Reduced
11:07 Operating Mode Changed to Cool Max
12:00 Controller Alarms: 53 - Battery Pack Failure
13:00 Controller Alarms: 53 - Battery Pack Failure
14:00 Controller Alarms: 53 - Battery Pack Failure
14:06 Defrost Initiated By Timer
14:41 Defrost Terminated Due to Normal Operation
14:50 Operating Mode Changed to Cool Reduced
14:51 Operating Mode Changed to Cool Max
15:00 Controller Alarms: 53 - Battery Pack Failure
16:00 Controller Alarms: 53 - Battery Pack Failure
17:00 Controller Alarms: 53 - Battery Pack Failure
17:51 Defrost Initiated By Timer
17:51 Operating Mode Changed to Defrost
18:00 Controller Alarms: 53 - Battery Pack Failure
18:27 Defrost Terminated Due to Normal Operation
18:42 Operating Mode Changed to Cool Max
18:45 Operating Mode Changed to Cool Reduced
19:00 Controller Alarms: 53 - Battery Pack Failure
19:08 Operating Mode Changed to Cool Max
19:54 Container ID Changed to ircu2002152
_______________________________________________________
May 11, 2016
Setpoint: -25.00, O2: OFF, CO2: OFF, Container: ircu2002152,
Serial : 04102615
2 Sensors Logged at 60 minute interval.
Sensor Format Resolution
Supply Average High
Return Average High
No Sensor Data
Time Event Data
19:55 Data Retrieval
_______________________________________________________